Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL122350-cgb battery12V235AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS
- Nominal Voltage: 12V
**Capacity**
- C10: 235Ah (at 25°C, 10.5V)
- Nominal Capacity (C10): 235Ah (at 25°C, 10.5V)
- C5 Capacity: 188Ah (at 25°C, 10.5V)
**Dimensions**
- Length: 547mm
- Width: 275mm
- Height: 242mm
- Total Height: 242mm
**Internal Resistance**
- Approximately 4.5 mΩ (at 25°C)
**Max Short-duration Discharge Current**
- 4230A (at 25°C)
**Weight**
- Approximately 82.5kg
**Terminal**
- RT-47

**■FEATURES**

- Special formula of grid alloys and lead paste, along with a unique manufacturing technique, ensuring high quality, high performance, and long lifespan.

- AGM valve-regulated sealing technology.

- High-strength ABS material used for the container and lid.

- Wide temperature range of application (-15~45°C).

- Optimal operating temperature (20±5°C).

- Leak-proof, safe, and reliable.

- Can be used in a standing or lying position, convenient for transportation and installation.

- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 12V

**Capacity**

- C10: 235Ah (at 25°C, 10.5V)

- Nominal Capacity (C10): 235Ah (at 25°C, 10.5V)

- C5 Capacity: 188Ah (at 25°C, 10.5V)

**Dimensions**

- Length: 547mm

- Width: 275mm

- Height: 242mm

- Total Height: 242mm

**Internal Resistance**

- Approximately 4.5 mΩ (at 25°C)

**Max Short-duration Discharge Current**

- 4230A (at 25°C)

**Weight**

- Approximately 82.5kg

**Terminal**

- RT-47

**■CHARGE**

| **Using Mode** | **Charging Voltage** | **Temperature Compensation** | **Max Charging Current** |

|------------------|------------------------|-----------------------------------|-----------------------------|

| Standby Use     | 2.275±0.025V/cell (25°C) | -3.3mV/°C/cell                        | 58.75A                        |

| Cyclic Use       | 2.45±0.05V/cell (25°C)     | -5mV/°C/cell                           | -                                    |

**■STORAGE**

- Batteries should be stored in a dry, clean warehouse with good air ventilation.

- Avoid direct sunlight and proximity to heat sources (such as radiators, with a distance of more than 1 meter).

- Keep away from any toxic gases and organic solvents.

- If the ambient temperature is below 25°C, the longest storage life is 6 months. For higher temperatures, refer to the specified durations in the table below:

  | **Storage Temperature (°C)** | ≤25   | 26~33 | 34~40 |

  |--------------------------------|-------|--------|--------|

  | **Storage Time (Month)**       | 6       | 3        | 1        |

- Batteries should be recharged within their storage life or before use.

- Charging method: Maximum charging current of 58.75A, constant voltage of 2.45±0.05V/cell (25°C); charging time: 15~20 hours; temperature compensation coefficient: -5mV/°C/cell.


INQUIRY