Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL122500-cgb battery12V250AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS**
- Nominal Voltage: 12V
**Capacity**
- C10: 250Ah (at 25℃, 10.5V)
- Nominal Capacity (C10): 250Ah (at 25℃, 10.5V)
- C5 Capacity: 200Ah (at 25℃, 10.5V)
**Dimensions**
- Length: 547mm
- Width: 275mm
- Height: 242mm
- Total Height: 242mm
**Internal Resistance**
- Approximately 2.2 mΩ (at 25℃)
**Max Short-duration Discharge Current**
- 4500A (at 25℃)
**Weight**
- Approximately 80.0kg
**Terminal**
- RT-47

**■FEATURES**

- Special formula of grid alloys and lead paste, along with a unique manufacturing technique, ensures high quality, high performance, and long life.

- AGM valve-regulated sealing technology.

- High-strength ABS material used for the container and lid.

- Wide temperature range of application (-15~45℃).

- Optimal operating temperature (20±5℃).

- Leak-free, safe, and reliable.

- Can be used standing or lying down, making them convenient to transport and install.

- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 12V

**Capacity**

- C10: 250Ah (at 25℃, 10.5V)

- Nominal Capacity (C10): 250Ah (at 25℃, 10.5V)

- C5 Capacity: 200Ah (at 25℃, 10.5V)

**Dimensions**

- Length: 547mm

- Width: 275mm

- Height: 242mm

- Total Height: 242mm

**Internal Resistance**

- Approximately 2.2 mΩ (at 25℃)

**Max Short-duration Discharge Current**

- 4500A (at 25℃)

**Weight**

- Approximately 80.0kg

**Terminal**

- RT-47

**■CHARGE**

| **Using Mode** | **Charging Voltage** | **Temperature Compensation** | **Max Charging Current** |

|------------------|--------------------------------|------------------------------------------|---------------------------------|

| Standby Use     | 2.275±0.025V/cell (25℃)  | -3.3mV/℃/cell                                 | 62.5A                                 |

| Cyclic Use         | 2.45±0.05V/cell (25℃)       | -5mV/℃/cell                                      | -                                        |

**■STORAGE**

- Batteries should be stored in a dry, clean, and well-ventilated warehouse.

- Avoid direct sunlight and keep away from heat sources (such as radiators, with a distance of more than 1 meter).

- Keep away from any toxic gases and organic solvents.

- If the ambient temperature is below 25℃, the longest storage life is 6 months. For higher ambient temperatures, refer to the specified storage time in the table below:

  | **Storage Temperature (℃)** | ≤25    | 26~33 | 34~40 |

  |------------------------------------|--------|---------|---------|

  | **Storage Time (Month)**          | 6        | 3          | 1           |

- Batteries should be recharged within the storage life or before use.

- Charging methods: Maximum charging current is 62.5A, constant voltage is 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.