Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL1272-cgb battery12V7.2AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS
**Nominal Voltage:** 12V
**Capacity:**
- C20: 7.2Ah (10.5V, at 25℃)
- C10: 6.48Ah (10.5V, at 25℃)
**Dimension:**
- Length: 151mm
- Width: 65mm
- Height: 94mm
- Total Height: 100mm
**Internal Resistance:** Approximately 25 mΩ (25℃)
**Max Short-duration Discharge Current:** 216A (25℃)
**Weight:** Approximately 2.4kg
**Terminal:** FO-02/FO-03

**■FEATURES**

- AGM valve regulated sealing technology;

- High strength ABS material for container & lid;

- Wide temperature scope of application (-15~45℃);

- Best temperature of application (20±5℃);

- No leaking, safe and reliable;

- Standing or lying down for using, convenient to transport and install;

- High sealed reaction efficiency, little loss of water, no need to add distilled water or electrolyte, simple to use and maintain;

- Low self-discharge rate.

**■SPECIFICATIONS**

**Nominal Voltage:** 12V

**Capacity:**

- C20: 7.2Ah (10.5V, at 25℃)

- C10: 6.48Ah (10.5V, at 25℃)

**Dimension:**

- Length: 151mm

- Width: 65mm

- Height: 94mm

- Total Height: 100mm

**Internal Resistance:** Approximately 25 mΩ (25℃)

**Max Short-duration Discharge Current:** 216A (25℃)

**Weight:** Approximately 2.4kg

**Terminal:** FO-02/FO-03

**■CHARGE**

| **Using Mode** | **Charging Voltage** | **Temperature Compensation** | **Max Charging Current** |

|----------------|-----------------------|------------------------------|--------------------------|

| Standby Use    | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell | 2.16A |

| Cyclic Use     | 2.45±0.05V/cell (25℃)   | -5mV/℃/cell   | (Information missing)  |

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with a good air exchange system. They should avoid direct sunlight and heat sources such as radiators (keeping a distance of more than 1m). Batteries should also be kept away from any toxic gases and organic solvents.

- The longest storage life is 6 months when the ambient temperature is less than 25℃. If the ambient temperature is higher, the storage life varies as specified in the table below:

| **Storage Temperature (℃)** | ≤25 | 26~33 | 34~40 |

|------------------------------|-----|---------|---------|

| **Storage Time (Month)**     | 6   | 3       | 1       |

- Batteries should be recharged within the storage life or before using.

- Charging methods: maximum charging current 2.16A, constant voltage 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.


INQUIRY