Specifications
- Nominal Voltage: 12V
- C10 Nominal Capacity: 230Ah (25℃, 10.5V)
- C5 Capacity: 184Ah (25℃, 10.5V)
- Dimensions:
- Length: 547mm
- Width: 275mm
- Height: 242mm
- Total Height: 242mm
- Internal Resistance: Approximately 4.5 mΩ (25℃)
- Max Short-duration Discharge Current: 4140A (25℃)
- Weight: Approximately 75.60kg
- Terminal: RT-47
**■Features**
- Special formula of grid alloys and lead paste, along with a special manufacturing technique, ensures high quality, high performance, and long life.
- Utilizes AGM valve regulated sealing technology.
- Container and lid made of high-strength ABS material.
- Wide temperature range of application (-15~45℃).
- Optimal operating temperature (20±5℃).
- Leak-free, safe, and reliable.
- Can be used in a standing or lying position, convenient for transportation and installation.
- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.
- Low self-discharge rate.
**■Specifications**
- Nominal Voltage: 12V
- C10 Nominal Capacity: 230Ah (25℃, 10.5V)
- C5 Capacity: 184Ah (25℃, 10.5V)
- Dimensions:
- Length: 547mm
- Width: 275mm
- Height: 242mm
- Total Height: 242mm
- Internal Resistance: Approximately 4.5 mΩ (25℃)
- Max Short-duration Discharge Current: 4140A (25℃)
- Weight: Approximately 75.60kg
- Terminal: RT-47
**■Charge**
| Operating Mode | Charging Voltage | Temperature Compensation | Max Charging Current |
|----------------|------------------|--------------------------|-----------------------|
| Standby Use | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell | 57.5A |
| Cyclic Use | 2.45±0.05V/cell (25℃) | -5mV/℃/cell | - |
**■Storage**
- Batteries should be stored in a dry, clean warehouse with good ventilation.
- Avoid direct sunlight and heat sources (e.g., radiators, maintain a distance of more than 1m).
- Keep away from any toxic gases and organic solvents.
- When the ambient temperature is below 25℃, the longest storage life is 6 months. If the ambient temperature is higher, the longest storage life varies as specified in the table below:
| Storage Temperature (℃) | ≤25 | 26~33 | 34~40 |
|--------------------------|-----|--------|--------|
| Storage Time (Month) | 6 | 3 | 1 |
- Batteries should be recharged within the storage life or before use.
- Charging methods: maximum charging current of 57.5A, constant voltage of 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.
Contact: Sales Representative: Mr. Xu
Phone: 19710409880
Tel: 400-1177-032
Email: 19710409880@139.com
Add: CGB-172 Checheng Avenue, Wuhan Economic and Technological Development Zone, Hubei Province, China