Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL122000A-cgb battery12V200AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS**
- Nominal Voltage: 12V
- C10 Nominal Capacity: 200Ah (25℃, 10.5V)
- C5 Capacity: 160Ah (25℃, 10.5V)
- Dimensions:
- Length: 522mm
- Width: 240mm
- Height: 218mm
- Total Height: 245mm
- Internal Resistance: Approximately 4.5 mΩ (25℃)
- Max Short-duration Discharge Current: 3600A (25℃)
- Weight: Approximately 70kg
- Terminal: FP-30/RT-34

**■FEATURES**

- Special formula of grid alloys and lead paste, along with special manufacturing techniques, ensure high quality, high performance, and long life.

- AGM valve regulated sealing technology.

- High strength ABS material for container & lid.

- Wide temperature scope of application (-15~45℃).

- Best temperature of application (20±5℃).

- No leaking, safe, and reliable.

- Can be used in a standing or lying position, convenient for transport and installation.

- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 12V

- C10 Nominal Capacity: 200Ah (25℃, 10.5V)

- C5 Capacity: 160Ah (25℃, 10.5V)

- Dimensions:

  - Length: 522mm

  - Width: 240mm

  - Height: 218mm

  - Total Height: 245mm

- Internal Resistance: Approximately 4.5 mΩ (25℃)

- Max Short-duration Discharge Current: 3600A (25℃)

- Weight: Approximately 70kg

- Terminal: FP-30/RT-34

**■CHARGE**

| Operating Mode | Charging Voltage | Temperature Compensation | Max Charging Current |

|------------|------------------|--------------------------|-----------------------|

| Standby Use | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell | 50A |

| Cyclic Use | 2.45±0.05V/cell (25℃) | -5mV/℃/cell | - |

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with good air exchange.

- Avoid direct sunlight and heat sources (such as radiators, maintain a distance of more than 1m).

- Keep away from any toxic gases and organic solvents.

- The longest storage life of the battery is 6 months when the ambient temperature is below 25℃. For higher ambient temperatures, refer to the specified storage time in the table below:

  | Storage Temperature (℃) | ≤25 | 26~33 | 34~40 |

  |--------------------------|------|-------|-------|

  | Storage Time (Month)     | 6    | 3     | 1     |

- Batteries should be recharged within their storage life or before use.

- Charging methods: Maximum charging current of 50A, constant voltage of 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.


INQUIRY