Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL62000-cgb battery6V200AH-Suitable for high-precision, high-performance UPS, EPS

Specifications
- Nominal Voltage: 6V
- Capacity (C10): 200Ah (25℃, 5.25V)
- Capacity (C5): 160Ah (25℃, 5.25V)
- Dimensions:
- Length: 322mm
- Width: 178mm
- Height: 225.5mm
- Total Height: 259.5mm
- Internal Resistance: Approximately 4 mΩ (25℃)
- Max Short-duration Discharge Current: 4000A (25℃)
- Weight: Approximately 35.67kg
- Terminal: FP-08/RT-58

**■Features**

- Special formula of grid alloys and lead paste, utilizing a special manufacturing technique to ensure high quality, high performance, and long life.

- AGM valve regulated sealing technology.

- High strength ABS material used for the container and lid.

- Wide temperature range of application (-15~45℃).

- Optimal operating temperature (20±5℃).

- Leak-proof, safe, and reliable.

- Can be used in a standing or lying position, making it convenient for transportation and installation.

- High sealed reaction efficiency with minimal water loss, eliminating the need to add distilled water or electrolyte, and making it simple to use and maintain.

- Low self-discharge rate.

**■Specifications**

- Nominal Voltage: 6V

- Capacity (C10): 200Ah (25℃, 5.25V)

- Capacity (C5): 160Ah (25℃, 5.25V)

- Dimensions:

  - Length: 322mm

  - Width: 178mm

  - Height: 225.5mm

  - Total Height: 259.5mm

- Internal Resistance: Approximately 4 mΩ (25℃)

- Max Short-duration Discharge Current: 4000A (25℃)

- Weight: Approximately 35.67kg

- Terminal: FP-08/RT-58

**■Charge**

| Operating Mode | Charging Voltage                  | Temperature Compensation | Max Charging Current |

|----------------|-----------------------------------|--------------------------|----------------------|

| Standby Use    | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell        | 60A                  |

| Cyclic Use     | 2.45±0.05V/cell (25℃)   | -5mV/℃/cell           |                          |

**■Storage**

- Batteries should be stored in a dry, clean warehouse with good air exchange.

- Avoid direct sunlight and heat sources (such as radiators).

- Keep away from any toxic gases and organic solvents.

- When the ambient temperature is below 25℃, the longest storage life is 6 months. For higher temperatures, refer to the storage time changes in the table below:

  - Storage Temperature (℃): ≤25   26~33  34~40

  - Storage Time (Month):       6        3         1

- Batteries should be recharged within the storage life or before use.

- Charging methods: maximum charging current of 60A, constant voltage of 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.


INQUIRY