Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

CBL61000-cgb battery6V100AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS
- Nominal Voltage: 6V
- Nominal Capacity (C10): 100Ah (at 25℃, 5.25V)
- Capacity (C5): 80Ah (at 25℃, 5.25V)
- Dimensions:
- Length: 195mm
- Width: 170mm
- Height: 206mm
- Total Height: 210mm
- Internal Resistance: Approximately 1.65 mΩ (at 25℃)
- Max Short-duration Discharge Current: 2000A (at 25℃)
- Weight: Approximately 17.8kg
- Terminal: RT-24

**■FEATURES**

- Special formula of grid alloys and lead paste, utilizing a special manufacturing technique, ensuring high quality, high performance, and long life.

- AGM valve regulated sealing technology.

- High strength ABS material for container & lid.

- Wide temperature scope of application (-15~45℃).

- Best operating temperature (20±5℃).

- Leak-free, safe, and reliable.

- Can be used standing or lying down, convenient for transportation and installation.

- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 6V

- Nominal Capacity (C10): 100Ah (at 25℃, 5.25V)

- Capacity (C5): 80Ah (at 25℃, 5.25V)

- Dimensions:

  - Length: 195mm

  - Width: 170mm

  - Height: 206mm

  - Total Height: 210mm

- Internal Resistance: Approximately 1.65 mΩ (at 25℃)

- Max Short-duration Discharge Current: 2000A (at 25℃)

- Weight: Approximately 17.8kg

- Terminal: RT-24

**■CHARGE**

| Operating Mode | Charging Voltage               | Temperature Compensation | Max Charging Current |

|----------------|--------------------------------|--------------------------|----------------------|

| Standby Use    | 2.275±0.025V/cell (25℃)      | -3.3mV/℃/cell           | 30A                  |

| Cyclic Use     | 2.45±0.05V/cell (25℃)        | -5mV/℃/cell             |                      |

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with good air exchange.

- Avoid direct sunlight and keep away from heat sources (such as radiators).

- Keep away from any toxic gases and organic solvents.

- When the ambient temperature is below 25℃, the longest storage life is 6 months. For higher temperatures, refer to the storage time variation in the table below:

  - Storage Temperature (℃): ≤25   26~33  34~40

  - Storage Time (Months):   6        3         1

- Batteries should be recharged within their storage life or before use.

- Charging methods: Maximum charging current is 30A, constant voltage is 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.


INQUIRY