Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

GEL61000AG-CGB battery6V100AH-gel battery for solar and wind power systems

SPECIFICATIONS
- Nominal Voltage: 6V
- Capacity:
- C10: 100Ah (25℃, 5.25V)
- C5: 80Ah (25℃, 5.25V)
- Dimensions:
- Length: 195mm
- Width: 170mm
- Height: 206mm
- Total Height: 210mm
- Internal Resistance: Approximately 1.65 mΩ (25℃)
- Max Short-duration Discharge Current: 2000A (25℃)
- Weight: Approximately 17.8kg
- Terminal: RT-24

**■FEATURES**

- Designed with flat plate, GEL electrolyte, and AGM separator technology.

- The GEL electrolyte inside the battery maintains uniformity, ensuring excellent cycle life.

- The GEL electrolyte possesses a significant thermal capacity, preventing thermal runaway phenomena.

- Constructed with high-strength ABS material for the container and lid.

- Wide temperature range of application (-15~45℃), with the optimal operating temperature being (20±5℃).

- Leak-proof, safe, and reliable.

- Can be used standing or lying down, making it convenient for transportation and installation.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 6V

- Capacity:

  - C10: 100Ah (25℃, 5.25V)

  - C5: 80Ah (25℃, 5.25V)

- Dimensions:

  - Length: 195mm

  - Width: 170mm

  - Height: 206mm

  - Total Height: 210mm

- Internal Resistance: Approximately 1.65 mΩ (25℃)

- Max Short-duration Discharge Current: 2000A (25℃)

- Weight: Approximately 17.8kg

- Terminal: RT-24

**■CHARGE**

- Using Mode: Standby Use

  - Charging Voltage: 2.275±0.025V/cell (25℃)

  - Temperature Compensation: -3.3mV/℃/cell

  - Max Charging Current: 30A

- Using Mode: Cyclic Use

  - Charging Voltage: 2.45±0.05V/cell (25℃)

  - Temperature Compensation: -5mV/℃/cell

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with a good air exchange system.

- Avoid direct sunlight and keep away from heat sources (such as radiators, with a distance of more than 1 meter).

- Avoid contact with any toxic gases and organic solvents.

- The longest storage life is 6 months when the ambient temperature is below 25℃. For higher temperatures, refer to the specified storage life in the table below:

| Storage Temperature (℃) | Storage Time (Month) |

|--------------------------|----------------------|

| ≤25                      | 6                    |

| 26~33                   | 3                    |

| 34~40                   | 1                    |

- Batteries should be recharged within the storage life or before use.

- Charging methods: Maximum charging current of 30A, constant voltage of 2.45±0.05V/cell (25℃). Charging time: 15~20 hours. Temperature compensation coefficient: -5mV/℃/cell.