Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

GEL122350AG-CGB battery12V235AH-gel battery for solar and wind power systems

SPECIFICATIONS
- Nominal voltage: 12V
- C10 nominal capacity: 235Ah (at 25℃, 10.5V)
- C5 capacity: 188Ah (at 25℃, 10.5V)
- Dimensions:
- Length: 547mm
- Width: 275mm
- Height: 242mm
- Total height: 242mm
- Internal resistance: Approximately 4.5 mΩ (at 25℃)
- Max short-duration discharge current: 4700A (at 25℃)
- Weight: Approximately 77.00kg
- Terminal: RT-47

**■FEATURES**

- Designed with flat plate, GEL electrolyte, and AGM separator technology.

- The GEL electrolyte maintains uniformity within the battery, resulting in excellent cycle life.

- The GEL electrolyte possesses a substantial thermal capacity, preventing thermal runaway phenomena.

- Constructed with high-strength ABS material for the container and lid.

- Wide temperature range of application (-15~45℃), with the optimal operating temperature being (20±5℃).

- Leak-proof, safe, and reliable.

- Can be used in a standing or lying position, making it convenient for transportation and installation.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal voltage: 12V

- C10 nominal capacity: 235Ah (at 25℃, 10.5V)

- C5 capacity: 188Ah (at 25℃, 10.5V)

- Dimensions:

  - Length: 547mm

  - Width: 275mm

  - Height: 242mm

  - Total height: 242mm

- Internal resistance: Approximately 4.5 mΩ (at 25℃)

- Max short-duration discharge current: 4700A (at 25℃)

- Weight: Approximately 77.00kg

- Terminal: RT-47

**■CHARGE**

- Charging modes:

  - Standby use:

    - Charging voltage: 2.275±0.025V/cell (at 25℃)

    - Temperature compensation: -3.3mV/℃/cell

    - Max charging current: 70.5A

  - Cyclic use:

    - Charging voltage: 2.45±0.05V/cell (at 25℃)

    - Temperature compensation: -5mV/℃/cell

**■STORAGE**

- Batteries should be stored in a dry, clean, and well-ventilated warehouse.

- Avoid direct sunlight and proximity to heat sources (such as radiators, maintaining a distance of more than 1 meter).

- Avoid contact with any toxic gases and organic solvents.

- The longest storage life is 6 months when the ambient temperature is below 25℃. For higher temperatures, refer to the specified conditions in the table below.

- Storage temperature (℃): ≤25, 26~33, 34~40

- Storage time (months): 6, 3, 1

- Batteries should be recharged within the storage life or before use.

- Charging method: maximum charging current of 70.5A, constant voltage of 2.45±0.05V/cell (at 25℃); charging time: 15~20 hours; temperature compensation coefficient: -5mV/℃/cell.


INQUIRY