CBL12350-cgb battery12V35AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS**
- Nominal Voltage: 12V
- Nominal Capacity (C10): 35Ah (25℃, 10.5V)
- Capacity (C5): 28Ah (25℃, 10.5V)
- Dimensions:
- Length: 198mm
- Width: 132mm
- Height: 170mm
- Total Height: 170mm
- Internal Resistance: Approximately 12 mΩ (25℃)
- Max Short-duration Discharge Current: 700A (25℃)
- Weight: Approximately 12.60kg
- Terminal: FP-39/RT-36

**■FEATURES**

- Special formula of grid alloys and lead paste, along with a special manufacturing technique, ensure high quality, high performance, and long life.

- AGM valve regulated sealing technology.

- High strength ABS material for the container and lid.

- Wide temperature scope of application (-15~45℃).

- Best temperature of application (20±5℃).


**■TERMINAL**

- No leaking, safe, and reliable.

- Can be used standing or lying down, making it convenient for transportation and installation.

- High sealed reaction efficiency, minimal loss of water, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 12V

- Nominal Capacity (C10): 35Ah (25℃, 10.5V)

- Capacity (C5): 28Ah (25℃, 10.5V)

- Dimensions:

  - Length: 198mm

  - Width: 132mm

  - Height: 170mm

  - Total Height: 170mm

- Internal Resistance: Approximately 12 mΩ (25℃)

- Max Short-duration Discharge Current: 700A (25℃)

- Weight: Approximately 12.60kg

- Terminal: FP-39/RT-36

**■CHARGE**

| Operating Mode | Charging Voltage               | Temperature Compensation | Max Charging Current |

|----------------|--------------------------------|--------------------------|----------------------|

| Standby Use    | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell           | 10.5A                |

| Cyclic Use     | 2.45±0.05V/cell (25℃)    | -5mV/℃/cell             |                      |

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with good air exchange.

- Avoid direct sunlight and proximity to heat sources (such as radiators).

- Batteries should be kept away from any toxic gases and organic solvents.

- The longest storage life is 6 months when the ambient temperature is less than 25℃. For higher temperatures, refer to the specified chart below:

  - Storage Temperature (℃):  ≤25   26~33  34~40

  - Storage Time (Month):        6       3         1

- Batteries should be recharged within the storage life or before use.

- Charging methods: Maximum charging current is 10.5A, constant voltage is 2.45±0.05V/cell (25℃); Charging time: 15~20 hours; Temperature compensation coefficient: -5mV/℃/cell.