CBL121000B-cgb battery12V100AH-Suitable for high-precision, high-performance UPS, EPS

SPECIFICATIONS
- Nominal Voltage: 12V
- C10 Nominal Capacity: 100Ah (25℃, 10.5V)
- C5 Capacity: 80Ah (25℃, 10.5V)
- Dimensions:
- Length: 329mm
- Width: 174mm
- Height: 214mm
- Total Height: 218mm
- Internal Resistance: Approximately 6.5 mΩ (25℃)
- Max Short-duration Discharge Current: 2000A (25℃)
- Weight: Approximately 32.94kg
- Terminal: FP-29/RT-22

**■FEATURES**

- Special formula of grid alloys and lead paste, along with a special manufacturing technique, ensure high quality, high performance, and long life.

- AGM valve regulated sealing technology.

- High-strength ABS material for container & lid.

- Wide temperature range of application (-15~45℃).

- Optimal application temperature (20±5℃).

- Leak-proof, safe, and reliable.

- Can be used standing or lying down, convenient for transportation and installation.

- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.

- Low self-discharge rate.

**■SPECIFICATIONS**

- Nominal Voltage: 12V

- C10 Nominal Capacity: 100Ah (25℃, 10.5V)

- C5 Capacity: 80Ah (25℃, 10.5V)

- Dimensions:

  - Length: 329mm

  - Width: 174mm

  - Height: 214mm

  - Total Height: 218mm

- Internal Resistance: Approximately 6.5 mΩ (25℃)

- Max Short-duration Discharge Current: 2000A (25℃)

- Weight: Approximately 32.94kg

- Terminal: FP-29/RT-22

**■CHARGE**

| Using Mode | Charging Voltage | Temperature Compensation | Max Charging Current |

|------------|------------------|--------------------------|----------------------|

| Standby Use | 2.275±0.025V/cell (25℃) | -3.3mV/℃/cell | 30A |

| Cyclic Use | 2.45±0.05V/cell (25℃) | -5mV/℃/cell | - |

**■STORAGE**

- Batteries should be stored in a dry and clean warehouse with good air exchange.

- Avoid direct sunlight and proximity to heat sources (such as radiators, maintain a distance of more than 1 meter).

- Keep batteries away from any toxic gas and organic solvents.

- The longest storage life is 6 months when the ambient temperature is below 25℃. If the temperature is higher, refer to the table below for the longest storage life.

  - Storage Temperature (℃): ≤25   26~33   34~40

  - Storage Time (Month): 6       3          1

- Batteries should be recharged within the storage life or before use.

- Charging methods: maximum charging current 30A, constant voltage 2.45±0.05V/cell (25℃); Charging time: 15~20h; Temperature compensation coefficient: -5mV/℃/cell.