Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

24OPzS3000-CGBbattery2V3000AH-communications power supply system battery

Specifications:
Nominal Voltage: 2V
Nominal Capacity (C10): 3000Ah (1.80V @ 20℃)
Dimensions:
Length: 576mm
Width: 212mm
Height: 771mm
Total Height: 826mm
Weight:
Without electrolyte: Approx. 155kg
With electrolyte: Approx. 218kg
Max Charging Current: 600A
Internal Resistance:
Fully Charged @ 20℃: 0.00045 Ohm

AGM Valve Regulated Lead Acid Battery (2V 3000Ah) - Transparent Casing Version

Features:

  • Transparent containers: Allows for easy inspection of the battery's internal condition.

  • Special filter installation for acid fog proof: Enhances safety by preventing acid mist leaks.

  • Special pole sealed technology: Provides excellent sealing performance to prevent leaks.

  • Maintenance convenient: The transparent casing allows for easy observation of the electrolyte level, making it convenient to add electrolyte when needed.

  • High quality and high reliability: Consistent performance for peace of mind.

  • Super long service life: Economical with a long service cycle.

Specifications:

  • Nominal Voltage: 2V

  • Nominal Capacity (C10): 3000Ah (1.80V @ 20℃)

  • Dimensions:

    • Length: 576mm

    • Width: 212mm

    • Height: 771mm

    • Total Height: 826mm

  • Weight:

    • Without electrolyte: Approx. 155kg

    • With electrolyte: Approx. 218kg

  • Max Charging Current: 600A

  • Internal Resistance:

    • Fully Charged @ 20℃: 0.00045 Ohm

  • Self Discharge:

    • 3% of capacity declined per month @ 20℃

  • Temperature Effect on Capacity (10HR)

    • Temperature | Capacity *---|---|

    • 40℃ | 109%

    • 20℃ | 100% (Rated Capacity)

    • 0℃ | 85%

    • -15℃ | 65%

Charging:

  • Using Mode | Charge Voltage (20℃) *---|---|

  • Cycle Use | 2.35~2.40V (-5mV/℃)

  • Float Use | 2.21~2.25V (-3mV/℃)

Please note:

  • This transparent casing version of the battery requires regular inspection of the electrolyte level and timely addition of qualified distilled water (if needed).

  • Adding electrolyte should be strictly in accordance with the manufacturer's instructions to avoid safety hazards or damage to the battery due to improper operation.

Differences from the non-transparent casing version:

  • This version features a transparent casing for easy viewing of the battery's internal condition and checking the electrolyte level.

  • This version is more suitable for applications that require frequent electrolyte level checks.

  • The non-transparent casing version may be slightly less expensive, but requires other methods (such as voltage measurement) to determine the electrolyte level.


INQUIRY