Specifications:
Nominal Voltage: 2V
Nominal Capacity (C10): 350Ah (1.80V @ 20℃)
Dimensions:
Length: 124mm
Width: 206mm
Height: 470mm
Total Height: 525mm
Weight:
Without electrolyte: Approx. 20.5kg
With electrolyte: Approx. 27kg
Max Charging Current: 70A
Internal Resistance:
Fully Charged @ 20℃: 0.00075 Ohm
AGM Valve Regulated Lead Acid Battery (2V 350Ah) - Transparent Casing Version
Features:
Transparent casing: Allows for easy inspection of the battery's internal condition.
Special filter for acid mist proof: Enhances safety by preventing acid mist leaks.
Special pole sealing technology: Provides excellent sealing performance to prevent leaks.
Convenient maintenance: The transparent casing allows for easy observation of the electrolyte level, making it convenient to add electrolyte when needed.
High quality and high reliability: Consistent performance for peace of mind.
Super long service life: Economical with a long service cycle.
Specifications:
Nominal Voltage: 2V
Nominal Capacity (C10): 350Ah (1.80V @ 20℃)
Dimensions:
Length: 124mm
Width: 206mm
Height: 470mm
Total Height: 525mm
Weight:
Without electrolyte: Approx. 20.5kg
With electrolyte: Approx. 27kg
Max Charging Current: 70A
Internal Resistance:
Fully Charged @ 20℃: 0.00075 Ohm
Self Discharge:
3% capacity decline per month @ 20℃
Temperature Effect on Capacity (10HR)
Temperature | Capacity *---|---|
40℃ | 109%
20℃ | 100% (Rated Capacity)
0℃ | 85%
-15℃ | 65%
Charging:
Using Mode | Charge Voltage (20℃) *---|---|
Cycle Use | 2.35~2.40V (-5mV/℃)
Float Use | 2.21~2.25V (-3mV/℃)
Please note:
This transparent casing version of the battery requires regular inspection of the electrolyte level and timely addition of qualified distilled water (if needed).
Adding electrolyte should be strictly in accordance with the manufacturer's instructions to avoid safety hazards or damage to the battery due to improper operation.
Differences from the non-transparent casing version:
This version features a transparent casing for easy viewing of the battery's internal condition and checking the electrolyte level.
This version is more suitable for applications that require frequent electrolyte level checks.
The non-transparent casing version may be slightly less expensive, but requires other methods (such as voltage measurement) to determine the electrolyte level.
Contact: Sales Representative: Mr. Xu
Phone: 19710409880
Tel: 400-1177-032
Email: 19710409880@139.com
Add: CGB-172 Checheng Avenue, Wuhan Economic and Technological Development Zone, Hubei Province, China