Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

HRL1250W-CGB battery12V50W-high rate long life battery suitable for UPS, EPS, and other emergency backup power supply equipment and uninterruptible power supply equipment

SPECIFICATIONS
Nominal Voltage: 12V
Nominal Capacity (C20): 13.0Ah (25℃, 10.5V)
Nominal Power (15min): 50W/Cell (25℃, 10.02V)
Weight: Approximately 3.97kg
Dimensions:
- Length: 151mm
- Width: 98mm
- Height: 94.5mm
- Total Height: 100mm
Terminal: FO-02/FO-03

■FEATURES

● Grid alloy and lead paste formulated with a special formula and manufactured using a unique technique to ensure high quality, high performance, and long lifespan.

● High-rate discharge performance, delivering ample energy output.

● AGM valve-regulated sealing technology employed.

● Container and lid crafted from high-strength ABS material.

● Wide temperature range of application (-15~45℃).

● Optimal operating temperature: 20±5℃.

● Leak-proof design ensures safety and reliability.

● Can be used in both standing and lying positions, facilitating easy transportation and installation.

● High sealed reaction efficiency with minimal water loss, eliminating the need for adding distilled water or electrolyte, simplifying usage and maintenance.

● Low self-discharge rate.

■SPECIFICATIONS

Nominal Voltage: 12V  

Nominal Capacity (C20): 13.0Ah (25℃, 10.5V)  

Nominal Power (15min): 50W/Cell (25℃, 10.02V)  

Weight: Approximately 3.97kg  

Dimensions:

- Length: 151mm

- Width: 98mm

- Height: 94.5mm

- Total Height: 100mm

Terminal: FO-02/FO-03  

Internal Resistance: Approximately 14 mΩ (25℃)  

Max Charging Current: 3.9A (25℃)  

Max Short-duration Discharge Current: 390A (25℃)  

Charging Voltage (Standby Use): 2.275±0.025V/cell (25℃)  

Temperature Compensation (Standby Use): -3.3mV/℃/cell  

Charging Voltage (Cyclic Use): 2.45±0.05V/cell (25℃)  

Temperature Compensation (Cyclic Use): -5mV/℃/cell


INQUIRY