HRL1224W-CGB battery12V24W-high rate long life battery suitable for UPS, EPS, and other emergency backup power supply equipment and uninterruptible power supply equipment

SPECIFICATIONS
Nominal VoltALage: 12V
Nominal Capacity (C20): 6Ah (at 25℃, 10.5V)
Nominal Power (15min): 24W/Cell (at 25℃, 10.02V)
Weight: Approx. 2.28kg
Dimension:
- Length: 151mm
- Width: 51mm
- Height: 94mm
- Total Height: 100mm
Terminal: FO-02/FO-03

■FEATURES

- Special formula of grid alloys and lead paste, employing special manufacturing techniques to ensure high quality, high performance, and long life.

- High-rate discharge performance, delivering high energy output.

- AGM valve-regulated sealing technology.

- High strength ABS material used for the container and lid.

- Wide temperature range of application (-15~45℃).

- Optimal operating temperature (20±5℃).

- Leak-free design ensures safety and reliability.

- Can be used in either standing or lying positions, making it convenient for transportation and installation.

- High sealed reaction efficiency with minimal water loss, eliminating the need to add distilled water or electrolyte, thus simplifying usage and maintenance.

- Low self-discharge rate.

■SPECIFICATIONS

Nominal VoltALage: 12V Nominal Capacity (C20): 6Ah (at 25℃, 10.5V)

Nominal Power (15min): 24W/Cell (at 25℃, 10.02V) Weight: Approx. 2.28kg

Dimension: 

  - Length: 151mm

  - Width: 51mm

  - Height: 94mm

  - Total Height: 100mm

Terminal: FO-02/FO-03

Internal Resistance: Approx. 17 mΩ (at 25℃)

Max Charging Current: 1.8A (at 25℃)

Max Short-duration Discharge Current: 180A (at 25℃)

Charging Voltage (Standby Use): 2.275±0.025V/cell (at 25℃)

Temperature Compensation (Standby Use): -3.3mV/℃/cell

Charging Voltage (Cyclic Use): 2.45±0.05V/cell (at 25℃)

Temperature Compensation (Cyclic Use): -5mV/℃/cell