Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

HRL12135W-CGB battery12V135W-high rate long life battery suitable for UPS, EPS, and other emergency backup power supply equipment and uninterruptible power supply equipment

SPECIFICATIONS
Nominal Voltage: 12V
Nominal Capacity (C10): 33Ah (at 25℃, 10.5V)
Nominal Power (15min): 135W/Cell (at 25℃, 10.02V)
Weight: Approximately 11.94kg
Dimensions:
- Length: 195.5mm
- Width: 130mm
- Height: 158mm
- Total Height: 179mm
Terminal: RT-17/FP-39

■FEATURES

● Utilizes a special formula of grid alloys and lead paste, employing a unique manufacturing technique to ensure high quality, high performance, and long lifespan.

● Demonstrates high-rate discharge performance, providing significant energy output.

● Incorporates AGM valve-regulated sealing technology for enhanced safety and reliability.

● Constructed with high-strength ABS material for the container and lid.

● Suitable for a wide temperature range (-15~45℃), with the optimal operating temperature range being 20±5℃.

● Designed to prevent leakage, ensuring safety and reliability during use.

● Can be positioned upright or lying down for convenient transportation and installation.

● Exhibits high sealed reaction efficiency, with minimal water loss and no need for additional distilled water or electrolyte, simplifying usage and maintenance.

● Features a low self-discharge rate, enhancing long-term performance.

■SPECIFICATIONS

Nominal Voltage: 12V

Nominal Capacity (C10): 33Ah (at 25℃, 10.5V)

Nominal Power (15min): 135W/Cell (at 25℃, 10.02V)

Weight: Approximately 11.94kg

Dimensions:

- Length: 195.5mm

- Width: 130mm

- Height: 158mm

- Total Height: 179mm

Terminal: RT-17/FP-39

Internal Resistance: Approximately 13 mΩ (at 25℃)

Max Charging Current: 9.9A (at 25℃)

Max Short-duration Discharge Current: 660A (at 25℃)

Charging Voltage (Standby Use): 2.275±0.025V/cell (at 25℃)

Temperature Compensation (Standby Use): -3.3mV/℃/cell

Charging Voltage (Cyclic Use): 2.45±0.05V/cell (at 25℃)

Temperature Compensation (Cyclic Use): -5mV/℃/cell


INQUIRY