Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

HRL12210W-CGB battery12V210W-high rate long life battery suitable for UPS, EPS, and other emergency backup power supply equipment and uninterruptible power supply equipment

SPECIFICATIONS
Nominal Voltage: 12V
Nominal Capacity (C10): 55Ah (25℃, at 10.5V)
Nominal Power (15min): 210W/Cell (25℃, at 10.02V)
Weight: Approximately 18.5kg
Dimensions:
- Length: 229mm
- Width: 138mm
- Height: 207mm
- Total Height: 228mm
Terminal: FP-14, FP-15/FP-22/RT-38

■FEATURES

- Special formula of grid alloys and lead paste, along with a special manufacturing technique, ensure high quality, high performance, and long life.

- High-rate discharge performance, providing high energy output.

- Utilizes AGM valve regulated sealing technology.

- Constructed with high strength ABS material for the container and lid.

- Wide temperature range of application (-15℃ to 45℃), with the optimal operating temperature being (20±5℃).

- Leak-proof, ensuring safety and reliability.

- Can be used in a standing or lying position, making it convenient for transportation and installation.

- High sealed reaction efficiency with minimal water loss, eliminating the need to add distilled water or electrolyte, making it simple to use and maintain.

- Low self-discharge rate.

■SPECIFICATIONS

Nominal Voltage: 12V  

Nominal Capacity (C10): 55Ah (25℃, at 10.5V)  

Nominal Power (15min): 210W/Cell (25℃, at 10.02V)  

Weight: Approximately 18.5kg  

Dimensions:

- Length: 229mm

- Width: 138mm

- Height: 207mm

- Total Height: 228mm

Terminal: FP-14, FP-15/FP-22/RT-38

Internal Resistance: Approximately 10 mΩ (25℃)

Max Charging Current: 16.5A (25℃)

Max Short-duration Discharge Current: 1100A (25℃)

Charging Voltage (Standby Use): 2.275±0.025V/cell (25℃)

Temperature Compensation (Standby Use): -3.3mV/℃/cell

Charging Voltage (Cyclic Use): 2.45±0.05V/cell (25℃)

Temperature Compensation (Cyclic Use): -5mV/℃/cell


INQUIRY