Welcome: Wuhan CGB Battery System Co., Ltd.
Language: Chinese ∷  English

SE670-CGB battery 6V7AH - Safety Fire Emergency Battery for Safety Fire Emergency System

Specifications:
Nominal Voltage: 6V
Capacity:
C20: 7Ah (5.25V, at 25°C)
C10: 6.3Ah (5.25V, at 25°C)
C3: 5.25Ah (5.25V, at 25°C)
C1: 4.2Ah (5.1V, at 25°C)
Dimensions: 151mm x 34mm x 94mm (total height 100mm)
Terminal: FO-02 / FO-03
Internal Resistance: Approx. 15 mΩ (25°C)
Max Short-Duration Discharge Current: 210A (25°C)
Weight: Approx. 1.15kg

AGM Valve Regulated Sealed Lead Acid Battery (7Ah)

This high-performance battery features AGM (Absorbent Glass Mat) technology, offering a safe and reliable power source for various applications.

Key Features:

  • AGM Valve Regulated Sealing: Leak-proof design for safe and worry-free operation.

  • Wide Operating Temperature: Performs well in a range of environments from -15°C to 45°C (best at 20±5°C).

  • Flexible Placement: Can be used upright or lying down for easy installation.

  • Low Maintenance: Sealed design minimizes water loss, eliminating the need for topping up with distilled water or electrolyte.

  • Low Self-Discharge: Holds its charge well even during storage.

Specifications:

  • Nominal Voltage: 6V

  • Capacity:

    • C20: 7Ah (5.25V, at 25°C)

    • C10: 6.3Ah (5.25V, at 25°C)

    • C3: 5.25Ah (5.25V, at 25°C)

    • C1: 4.2Ah (5.1V, at 25°C)

  • Dimensions: 151mm x 34mm x 94mm (total height 100mm)

  • Terminal: FO-02 / FO-03

  • Internal Resistance: Approx. 15 mΩ (25°C)

  • Max Short-Duration Discharge Current: 210A (25°C)

  • Weight: Approx. 1.15kg

Charging:

  • Standby Use: 2.275±0.025V/cell (25°C) with -3.3mV/℃/cell temperature compensation

  • Cyclic Use: 2.45±0.05V/cell (25°C) with -5mV/℃/cell temperature compensation

  • Max Charging Current: 2.1A

Storage:

  • Store in a dry, clean, well-ventilated warehouse away from direct sunlight, heat sources (over 1m distance), and toxic gases/organic solvents.

  • Recharge every 6 months at temperatures below 25°C. Refer to the chart for storage times at higher temperatures.

  • Recharge method: constant voltage 2.45±0.05V/cell (25°C) with maximum charging current of 2.1A for 15-20 hours. Temperature compensation coefficient: -5mV/℃/cell.


INQUIRY