HR12400W-CGB battery12V400W-high-rate battery suitable for UPS, EPS, and other emergency backup power supply equipment and uninterruptible power supply equipment

SPECIFICATIONS
Nominal Voltage: 12V
Nominal Capacity (C10): 100Ah (25℃, at 10.5V)
Nominal Power (15min): 400W/Cell (25℃, at 10.02V)
Weight: Approximately 34.0kg
Dimension:
- Length: 329mm
- Width: 174mm
- Height: 214mm
- Total Height: 218mm
- Terminal: FP-29/RT-22

■FEATURES

- High-rate discharge performance, high energy

- AGM valve regulated sealing technology

- High strength ABS material for container & lid

- Wide temperature scope of application (-15~45℃)

- Best temperature of application (20±5℃)

- No leaking, safe and reliable

- Can be used standing or lying down, convenient for transport and installation

- High sealed reaction efficiency, little loss of water, no need to add distilled water or electrolyte, simple to use and maintain

- Low self-discharge rate

■SPECIFICATIONS

Nominal Voltage: 12V

Nominal Capacity (C10): 100Ah (25℃, at 10.5V)

Nominal Power (15min): 400W/Cell (25℃, at 10.02V)

Weight: Approximately 34.0kg

Dimension:

- Length: 329mm

- Width: 174mm

- Height: 214mm

- Total Height: 218mm

- Terminal: FP-29/RT-22

- Internal Resistance: Approximately 6.5 mΩ (25℃)

- Max Charging Current: 30A (25℃)

- Max Short-duration Discharge Current: 2000A (25℃)

Charging Voltage:

- Standby Use: 2.275±0.025V/cell (25℃)

- Temperature Compensation (Standby Use): -3.3mV/℃/cell

- Cyclic Use: 2.45±0.05V/cell (25℃)

- Temperature Compensation (Cyclic Use): -5mV/℃/cell


INQUIRY