SPECIFICATIONS
- Nominal Voltage: 12V
- Nominal Capacity (C10): 150Ah (10.5V, at 25℃)
- Nominal Capacity (C5): 120Ah (10.5V, at 25℃)
- Length: 483mm
- Width: 170mm
- Height: 241mm
- Total Height: 241mm
- Internal Resistance: Approximately 4.5 mΩ (25℃)
- Max Short-duration Discharge Current: 3000A (25℃)
- Weight: Approximately 46.3kg
- Terminal: FP-31/RT-32
**■ FEATURES**
- Special formula of grid alloys and lead paste, along with special manufacturing techniques, ensure high quality, high performance, and long lifespan.
- AGM valve regulated sealing technology.
- High-strength ABS material used for container and lid.
- Wide temperature range of application (-15~45℃).
- Optimal operating temperature (20±5℃).
- Leak-free, safe, and reliable.
- Can be used standing or lying down, making them convenient to transport and install.
- High sealed reaction efficiency, minimal water loss, no need to add distilled water or electrolyte, simple to use and maintain.
- Low self-discharge rate.
**■ SPECIFICATIONS**
- Nominal Voltage: 12V
- Nominal Capacity (C10): 150Ah (10.5V, at 25℃)
- Nominal Capacity (C5): 120Ah (10.5V, at 25℃)
- Length: 483mm
- Width: 170mm
- Height: 241mm
- Total Height: 241mm
- Internal Resistance: Approximately 4.5 mΩ (25℃)
- Max Short-duration Discharge Current: 3000A (25℃)
- Weight: Approximately 46.3kg
- Terminal: FP-31/RT-32
**■ CHARGE**
**Using Mode** **Charging Voltage** **Temperature Compensation** **Max Charging Current**
- Standby Use: 2.275±0.025V/cell (25℃), -3.3mV/℃/cell, 45A
- Cyclic Use: 2.45±0.05V/cell (25℃), -5mV/℃/cell
**■ STORAGE**
- Batteries should be stored in a dry and clean warehouse with good air exchange. They should be kept away from direct sunlight and heat sources (such as radiators) by a distance of more than 1m. Batteries should also be kept away from any toxic gases and organic solvents.
- If the ambient temperature is below 25℃, the longest storage life is 6 months. For higher temperatures, the longest storage life varies as shown in the table below:
| Storage Temperature (℃) | ≤25 | 26~33 | 34~40 |
|------------------------|----|-------|-------|
| Storage Time (Month) | 6 | 3 | 1 |
- Batteries should be recharged within the storage life or before use. The charging method involves a maximum charging current of 45A, constant voltage of 2.45±0.05V/cell (25℃), with a charging time of 15~20 hours and a temperature compensation coefficient of -5mV/℃/cell.
Contact: Sales Representative: Mr. Xu
Phone: 19710409880
Tel: 400-1177-032
Email: 19710409880@139.com
Add: CGB-172 Checheng Avenue, Wuhan Economic and Technological Development Zone, Hubei Province, China